1) Will both the detection and agent delivery work as designed regardless of the position of the ram? Units that mount on one side of the ram may not detect a fire starting on the other side of the ram or may not deliver agent effectively to properly suppress the growing fire.

2) Can the system interface with the machine controls to shut down the machine and interface with a local alarm or a paging system? If there is a fire, quick shutdown of the unit will help fight re-ignition of the fire. The interface will ensure that a problem will be quickly rectified and that the machine is returned to service in a timely manner, helping to avoid missed deadlines and to optimize production.

3) Be certain to select a fire suppressing agent that will effectively suppress the fire, but not contaminate the machine’s oil. Replacement of oil costs money and time. Use of clean agent alternatives like CO2 will effectively fight the fire and not add contaminates to the oil should a discharge occur.

4) Use detection that will be fast, but reliable. Some optical type detection systems will operate quickly, but may be prone to false discharges due to other processes in the factory—sometimes as simple as a lit cigarette or a torch.

False discharges can interrupt produc-tion and also disable the fire suppression system until the unit can be reset, leaving a machine unprotected. Alternatively, sprinkler-head type fire suppression units frequently require a great deal of heat build-up before activating, potentially delaying suppression long enough for damage to be done to the unit or for the fire to spread beyond the machine.

5) Where possible, ensure that the system uses a minimal amount of metal near the oil’s surface. With the electrical dis-charge from these machines, less metal in the portions of the fire suppression that are near the oil is very desirable.

While fire suppression is a critical part of a shop’s safety equipment, it does not make up for improper use of these machines. Always be certain to follow the manufacturer’s instructions and warnings for the operation of the machine. Never circumvent or disable safety features on a machine regardless of the presence of a fire suppression system.

It is impossible for those who have never seen one of these fires to fully appreciate the speed at which they grow or the danger they present. Following proper maintenance and use procedures on these machines coupled with the added safety of a fire suppression system can help ensure that a shop will not feel the effects of one of these machine, and frequently business, crippling events.

About First-rate Mold Solution Co. Ltd.
First-rate Mold Solution Co., Ltd. is based in China and engaged in supply of industry design,mold design,mold manufacturing,molding analysis,project management service,Our team has rich experience in the mold industry, We have first-class engineers in the fields of mold design, injection molding, metal stamping, metal die-casting, hot press molding and etc, we are enthusiastic to our industry and sufficiently inquisitive to learn,eternal adherents of leading-edge technologies in industrial design and manufacturing, such as the Mold technology in the United States, Germany mold technology, the mould technology in the United Kingdom, France mould technology,Italy mold technology, Japan mold technology and so on.

About firstratemold.com
our website has a lot of professional knowledge in mold industry in our blog and news section, also we are interested in CAD/CAM/CAE integration technology, such as AUTOCAD,UGNX, PRO/E,CATIA, CIMATRON, SOLIDWORKS, MOLDFLOW and so on,we warmly welcome every professional engineer, every mold maker and all those peoples who are interested in industrial design, mold design, mold manufacturing, injection mold, metal stamping mold, die-casting mold, injection molding,plastic product and other molds for industrial use to our blog and news section,we would like to share with them.